Master Control Unit

  • Small, ruggedized enclosure with wall mount, rack mount options (DIN rail optional)
  • Serial, and Digital I/O connectivity in every single device (Optional Ethernet/CDMA)
  • RS232, Serial ports, TCP access, COM port redirection (RS422/485 optional)
  • 21xAnalog ports with Sampling rates up to 10ksps
  • Monitoring of Fuel Tanks up to 22000 liters*
  • 4xDigital outputs for controlling BTS power sources
  • Split core CTs for easy installations
  • 6x Digital inputs for manual control of power sources
  • Self-Recovery Algorithms to make the system fail safe
  • Automated detachment from Power Source control to ensure uninterrupted power to the system in case of system failure
  • Digital Alarms and ACP-Feedback provision for DDF patch for easy integration with Client’s NOC
  • Access the unreachable-manage equipment behind remote firewalls and VPNs
  • Monitor and control environment of the data centers and remote sites
  • Enhanced Security for connection over public cellular network, VPN, SSH, AAA
  • Scan remote data and create proactive custom solutions
  • Easy troubleshooting with ON and off line data logging with time stamps
  • Even tracking and corrective actions- alert notification, Custom auto response
  • High data speeds for back up remote network connection
  • Serial port Management
  • Tunneled Serial Bridging
  • Port triggers with SNMP and email alerts
  • Offline data logging (Syslog, NFS, CIFS0
  • Multiple users per port (with port sniffing)
  • Access by TCP port
  • Telnet/ Unauthenticated Telnet SSH/ Raw TCP connect
  • RFC2217- Port redirection
  • No limits on number of hosts being concurrently accessed through one tunnel
  • No limits on number of clients who can access the one cellular router
Parameter Operating conditions Minimum Typical Maximum Unit
Operating Voltage 12.5 13.5 17 Volts
Power consumed 1.5 1.5 1.9 Watts
Operating Temperature -20°C +55°C
Storage Temperature -30°C +85°C
Number of Temperature Sensors 1 Units
Temperature Measurement Range 0°C to +100°C 0°C +100°C °C
Thermometer accuracy 0°C to +100°C ±0.2 ±0.5 ±1 °C
Number of Digital Inputs 10 Units
Number of Spare Ports 5
ADC Frequency 500 8000 KHz
(UART) M2M communication 9600 Bps
  • EN55024: 1998+A1:2001+A2:2003
  • IEC61000-4.2:1995 ESD 8kV Air Discharge (Direct), 4kV Contact Discharge (Direct/Indirect)
  • IEC61000-4.3:1995 Radiated Immunity 3.0 V/m, 1kHz, AM Sine Wave at 80%
  • IEC61000-4.5: 1995 Surge Immunity 1.0kV Common Mode, 1.0KV Differential Mode
  • IEC61000-4.6: 1996 Conducted Immunity 3.0Vrms, 80% AM modulated (1kHz)
  • IEC61000-4.11: 1994 Voltage Dips and Interrupts (>95%, 0.5periods), (30%, 25 periods), (>95%, 250 periods)
  • ROHS
  • CE (2011/65/EU)