UPS Monitoring Module

  • Small, ruggedized enclosure with wall mount brackets (DIN rail optional)
  • Hi speed data communication using CAN2.0 interface for M2M communication
  • 11 channels ADC having sampling speeds up to 10ksps
  • Small form factor with waterproof NEMA enclosure option
  • Accessible without a public IP
  • Network UPS tolls for UPS monitoring and Management
  • PDU and RPS management
  • Hotkey for in-session power menu
  • Monitors and assess the state of state of Rectifiers by monitoring the voltage and current of batteries as well as the total load of Rectifier
  • Fully scalable architecture to monitor new Rectifier installations without modifying the current installations
  • Wide AC and DC input voltage range
  • Optional data logging capabilities
  • 4 Digital I/O , 2RS232 ports, TCP access (RS422, RS485 option)
  • Configurable for standalone UPS Monitoring System with GSM/GPRS/Ethernet/CDMA connectivity.
  • Online and offline data storage option
  • Enhanced security for public internet connections using VPN, SSH, AAA
  • Programmable alert notifications and alarms
  • Industrial grade solution for use in demanding and tough environments
Parameter Type Operating conditions Minimum Typical Maximum Unit
Operating Voltage – 12.5 13.5 17 Volts
Power consumed 1.5 1.5 1.9 Watts
Number of Temperature Sensors – – 1 – Units
Temp Measurement Range 0°C to +100°C 0°C – +100°C °C
Thermometer accuracy 0°C to +100°C ±0.2 ±0.5 ±1 °C
Battery Bank Voltage DC – 0 – 560 VDC
Battery Bank Current -500 – 500 DCI
UPS Phase Voltages 3 phase, 4 Wire 0 220 400 VAC
Voltage measurement accuracy 0°C to +100°C – 0.01 – VAC
UPS Phase Currents 0 – 800A ACI
Current measurement accuracy 0°C to +100°C – 0.01 – Amp (AC)
ADC Resolution – – 10 – Bits
ADC Frequency – – 500 8000 KHz
M2M communication UART – – 9600 – Bps
M2M communication CAN Bus – – 125000 – Bps
  • EN55024: 1998+A1:2001+A2:2003
  • IEC61000-4.2:1995 ESD 8kV Air Discharge (Direct), 4kV Contact Discharge (Direct/Indirect)
  • IEC61000-4.3:1995 Radiated Immunity 3.0 V/m, 1kHz, AM Sine Wave at 80%
  • IEC61000-4.5: 1995 Surge Immunity 1.0kV Common Mode, 1.0KV Differential Mode
  • IEC61000-4.6: 1996 Conducted Immunity 3.0Vrms, 80% AM modulated (1kHz)
  • IEC61000-4.11: 1994 Voltage Dips and Interrupts (>95%, 0.5periods), (30%, 25 periods), (>95%, 250 periods)
  • ROHS
  • CE (2011/65/EU)
  • Isolation
  • Serial Port: 4kV ESD protection on RS232 and CAN Transceivers
  • Optional Chassis ground for signal integrity (Applicable for Metal casing models only)
  • 4kV ESD protection between Analog front end and Processor Core.
  • Complete Isolation between Analog front end and processor core preserving signal integrity and reducing noise
  • MOVs to protect against high voltage impulses