Rectifier Monitoring Module

  • Small, ruggedized enclosure with wall mount brackets (DIN rail optional)
  • Hi speed data communication using CAN2.0 interface for M2M communication
  • 11 channels ADC having sampling speeds up to 10ksps
  • Small form factor with waterproof NEMA enclosure option
  • Accessible without a public IP
  • Monitors and assess the state of state of Rectifiers by monitoring the voltage and current of batteries as well as the total load of Rectifier
  • Fully scalable architecture to monitor new Rectifier installations without modifying the current installations
  • Optional data logging capabilities
  • Digital I/O , 2RS232 ports, TCP access (RS422, RS485 option)
  • Configurable for standalone Rectifier Monitoring System with GSM/GPRS/Ethernet/CDMA connectivity.
  • Online and offline data storage option
  • Enhanced security for public internet connections using VPN, SSH, AAA
  • Programmable alert notifications and alarms
  • Industrial grade solution for use in demanding and tough environments
Parameter Type Operating conditions Min Typical Max Unit
Operating Voltage 12.5 13.5 17 Volts
Power consumed 1.5 1.5 1.9 Watts
No. of Temperature Sensors 1 Units
Temperature Measurement Range 0°C to +100°C 0°C +100°C °C
Thermometer accuracy 0°C to +100°C ±0.2 ±0.5 ±1 °C
Battery Bank Voltage DC Battery Bank Voltage 0 100 VDC
Battery Bank Current -500 500 DCI
Rectifier Load Current -800 800 ADC
Number of Spare Ports 1
ADC Resolution 10 Bits
ADC Frequency 500 8000 KHz
M2M communication UART 9600 Bps
ADC Frequency CAN Bus 125000 Bps
Operating Voltage 12.5 13.5 17 Volts
Power consumed 1.5 1.5 1.9 Watts
  • EN55024: 1998+A1:2001+A2:2003
  • IEC61000-4.2:1995 ESD 8kV Air Discharge (Direct), 4kV Contact Discharge (Direct/Indirect)
  • IEC61000-4.3:1995 Radiated Immunity 3.0 V/m, 1kHz, AM Sine Wave at 80%
  • IEC61000-4.5: 1995 Surge Immunity 1.0kV Common Mode, 1.0KV Differential Mode
  • IEC61000-4.6: 1996 Conducted Immunity 3.0Vrms, 80% AM modulated (1kHz)
  • IEC61000-4.11: 1994 Voltage Dips and Interrupts (>95%, 0.5periods), (30%, 25 periods), (>95%, 250 periods)
  • ROHS
  • CE (2011/65/EU)
  • Serial Port: 4kV ESD protection on RS232 and CAN Transceivers
  • Optional Chassis ground for signal integrity (Applicable for Metal casing models only)
  • Complete Isolation between Analog front end and processor core preserving signal integrity and reducing noise