Power Monitoring Module

  • Small, ruggedized enclosure with wall mount brackets (DIN rail optional)
  • 6 channels ADC having sampling speeds up to 10ksps
  • Small form factor with waterproof NEMA enclosure option
  • Monitors and assess the state of 1(one) ATS with optional control
  • Optional data logging capabilities
  • Optional Integration with Master Control Unit
  • Enhanced security for public internet connections using VPN, SSH, AAA
  • Programmable alert notifications and alarms
  • Industrial grade solution for use in demanding and tough environments
Parameter Type Operating conditions Min Typical Max Unit
Operating Voltage 12.5 13.5 17 Volts
Power consumed 1.5 1.5 1.9 Watts
ATS Phase Voltages 3 phase, 4 Wire 0 220 400 VAC
Voltage measurement accuracy 0°C to +100°C 0.01  VAC
ATS State Generator 170 220 400 VAC
CP 170 220 400 VAC
ATS Phase Currents 0 800A ACI
Current measurement accuracy 0°C to +100°C 0.01 Amp (AC)
CT measuring frequency 10 50 10000 Hz
ADC Resolution 10 Bits
ADC Frequency 500 8000 KHz
M2M communication  UART 9600 Bps
  • 2xTerminal blocks for easy installations
  • Optional Chassis ground for signal integrity (Applicable for Metal casing models only)
  • ROHS
  • CE (2011/65/EU)
  • EN55024: 1998+A1:2001+A2:2003
  • IEC61000-4.2:1995 ESD 8kV Air Discharge (Direct), 4kV Contact Discharge (Direct/Indirect)
  • IEC61000-4.3:1995 Radiated Immunity 3.0 V/m, 1kHz, AM Sine Wave at 80%
  • IEC61000-4.5: 1995 Surge Immunity 1.0kV Common Mode, 1.0KV  Differential Mode
  • IEC61000-4.6: 1996 Conducted Immunity 3.0Vrms, 80% AM modulated (1kHz)
  • IEC61000-4.11: 1994 Voltage Dips and Interrupts (>95%, 0.5periods), (30%, 25 periods), (>95%, 250 periods)